Trifluorobromomethane
|
CAS
75-63-8
|
CBrF3
|
RTECS
PA5425000
|
Synonyms & Trade Names
Bromotrifluoromethane, Fluorocarbon 1301, Freon® 13B1, Halocarbon 13B1, Halon® 1301, Monobromotrifluoromethane, Refrigerant 13B1, Trifluoromonobromomethane
|
DOT ID & Guide
1009 / 126
|
Exposure Limits
|
NIOSH REL: TWA 1000 ppm (6100 mg/m3)
|
OSHA PEL: TWA 1000 ppm (6100 mg/m3)
|
IDLH
40,000 ppm
See: 75638
|
Conversion
1 ppm = 6.09 mg/m3
|
Physical Description
Colorless, odorless gas. [Note: Shipped as a liquefied compressed gas.]
|
MW: 148.9
|
BP: -72°F
|
FRZ: -267°F
|
Sol: 0.03%
|
VP: >1 atm
|
IP: 11.78 eV
|
RGasD: 5.14
|
|
Fl.P: NA
|
UEL: NA
|
LEL: NA
|
|
Nonflammable Gas
|
Incompatibilities & Reactivities
Chemically-active metals (such as calcium, powdered aluminum, zinc & magnesium)
|
Measurement Methods
NIOSH 1017
See: NMAM or OSHA Methods |
Personal Protection & Sanitation (See protection)
Skin: Frostbite
Eyes: Frostbite
Wash skin: No recommendation
Remove: No recommendation
Change: No recommendation
Provide: Frostbite wash
|
First Aid (See procedures)
Eye: Frostbite
Skin: Frostbite
Breathing: Respiratory support
|
Respirator Recommendations
NIOSH/OSHA
Up to 10,000 ppm: (APF = 10) Any supplied-air respirator
Up to 25,000 ppm: (APF = 25) Any supplied-air respirator operated in a continuous-flow mode
Up to 40,000 ppm: (APF = 50) Any supplied-air respirator that has a tight-fitting facepiece and is operated in a continuous-flow mode (APF = 50) Any self-contained breathing apparatus with a full facepiece (APF = 50) Any supplied-air respirator with a full facepiece
Emergency or planned entry into unknown concentrations or IDLH conditions: (APF = 10,000) Any self-contained breathing apparatus that has a full facepiece and is operated in a pressure- demand or other positive-pressure mode (APF = 10,000) Any supplied-air respirator that has a full facepiece and is operated in a pressure-demand or other positive-pressure mode in combination with an auxiliary self-contained positive-pressure breathing apparatus
Escape: (APF = 50) Any air-purifying, full-facepiece respirator (gas mask) with a chin-style, front- or back-mounted organic vapor canister/Any appropriate escape-type, self-contained breathing apparatus
Important additional information about respirator selection
|
Exposure Routes
inhalation, skin and/or eye contact (liquid)
|
Symptoms
Dizziness; cardiac arrhythmias; liquid: frostbite
|
Target Organs
central nervous system, heart
|
See also: INTRODUCTION
See ICSC CARD: 0837 |